WETT Inspections for Barrie | Orillia | Midland | Alliston

Certified WETT Inspections for Wood Stoves, Fireplaces, Pellet Stoves and Boilers

Open Menu

Definition of WETT Inspection

The term “WETT Inspection” is a type of evaluation inspection conducted on a solid fuel burning appliance, and equipment by a WETT Damaged Mortar Joint in Fluetrained, WETT certified inspector.  A WETT Inspector makes observations when able and reports his or her findings in WETT Inc’s inspection and reporting procedures.  There are three different levels of WETT Inspections available, level 1 WETT Inspections, Level 2 WETT Inspections, and Level 3 WETT Inspections. The WETT Inspector must be qualified under WETT’s various designation certificates to perform the applicable level of inspection.

 

Choose the right Level of WETT Inspection

A Level 1 WETT inspection is all that most Insurance Companies, Building Departments and Real Estate transactions require. Depending on your circumstances a higher level of inspection maybe required. 

Levels of WETT Inspection

 

LEVEL- ONE INSPECTION (READILY ACCESSIBLE)

​1.1 (A) DEFINITION

​Readily Accessible is defined as quickly or easily reached for inspection.

A level-1 inspection does not require the use of special tools for the opening or removal of any panel, door, covering, or
system components; nor (unless at the discretion of the inspector and client) would it require the use of ladders.

An inspector should be able to inspect any movable components of the fireplace, appliance or venting system that are readily
accessible. Examples would be components utilized during normal operation or visual inspection by the user of the system,
such as readily accessible loading doors, primary combustion chamber, ash pan doors, clean out doors, dampers, air controls,
etc.

A tape measure, light, mirror, camera, magnet, selfie-stick and/or other basic tools should comprise (but are not limited to) the
typical tools required to perform for this level of inspection.

​1.2 (A) GUIDELINES — GENERAL

A level-1 inspection includes:
1) a determination for compliance of readily accessible system components, including the proper use of required
components, their required clearances to combustibles, their proper support, as well as their condition and structural
integrity,
2) a determination for compliance of readily accessible shielding, outdoor air components, enclosures and duct work, if
present,
3) readily accessible evidence of operating malfunction, which may include but is not limited to smoke spillage,
4) obstructions and combustible deposits visible through readily accessible clean out doors or inspection ports.

​LEVEL- TWO INSPECTION (ACCESSIBLE)

2.1 (A) DEFINITION

Accessible is defined as able to be reached for the purpose of inspection, without the use of invasive methods to access areas of
the building, property or components of the solid-fuel-burning system.

Access may require the moving or removal of doors, panels, other coverings or system components, and will require the use of
ladders and common tools typically used by a WETT-certified chimney sweep or technician.

Accessible system and/or building components can be re-positioned to their original location and/or condition.

​​2.2 (A) GUIDELINES — GENERAL

A level-2 inspection includes (in addition to all aspects of a level-1 inspection):
1) continuity of accessible venting system and/or duct work components,
2) proper use and suitability of accessible venting system and/or duct work components, supports and mechanical
connections, including proper sizing,
3) internal and external surfaces of accessible system components for damage and/or deterioration, for freedom from
combustible deposits, blockage or obstructions and for evidence of operating malfunction,
4) surroundings and/or enclosures of accessible system components for proper clearances and construction. The inspection
may include locations within attics, crawl spaces and basements that can be accessed through doors, hatches or other
openings that do not require removal of parts of the building construction (that are) considered to be permanently
attached.

​LEVEL- THREE INSPECTION (CONCEALED ACCESSIBILITY)

3.1 (A) DEFINITION

Concealed Accessibility is defined as not able to be accessed except by invasive methods.

Access to concealed areas would require the removal of constructed property and/or system components by invasive methods,
for the purpose of implementing a level-3 inspection. This may require the use of specialty tools and equipment, such as a
video scanning device or flue tile removal system.

It may not be possible to reposition the removed property or system components to their original location and/or condition.
A permit would be required by the Authority Having Jurisdiction when compromising structural building components.

​3.2 (A) GUIDELINES — GENERAL

A level-3 inspection includes all aspects of a level-2 inspection plus:
1) the examination of concealed areas within, around and enclosing the system components for evidence of non-compliance,
malfunction, suspected hazards and/or damage to system or building components, and
2) surroundings and/or enclosures of concealed system components for proper clearances.

​3.2 (B) GUIDELINES — INVASIVE

Examples of invasive methods may include:
1) drilling or cutting holes through the surface of an enclosure wall (chase) to insert a camera or video scanning device,
2) removing a thimble or breech pipe,
3) removing masonry or other non-combustible materials to expose suspected combustible material,
4) removing or cutting a section of drywall or plaster that may conceal an abandoned chimney breech hole,
5) removal of facings or flashings to expose suspected hazards or deterioration, or other invasive methods as required, to
expose concealed areas for inspection.

​3.2 (C) ADDITIONAL DOCUMENTATION

When it is necessary to access and/or remove constructed property (or system components), the inspector and client must sign
a consent form:
1) to outline what invasive method(s) will be taken, as well as the means to access the concealed area(s), and
2) to outline the responsibilities of each party in regard to the condition the property will be left upon completion of the
level-3 inspection.